What should I do if the zero live wire is live?

2020-11-25 14:34:34 浙江立洲線纜股份有限公司 Viewd 3565

I. Introduction.


The AC power cord is divided into a neutral wire, the symbol letter is'N' and the fire wire, and the symbol letter is'L'. Also connected to electrical appliances is the ground wire-the wire connected to the earth;


The live wire, neutral wire, and ground wire are all wires connected to the three-hole socket, and a sinusoidal oscillation pressure difference is maintained between the live wire and the neutral wire. Since the earth and the neutral wire have the same potential, the live wire and the ground wire also maintain a sinusoidal oscillation pressure difference.




When the human body touches the live line, the person is standing on the ground. The current of the live line flows into the ground or the neutral line through the human body, and an electric shock will occur, while the neutral line will not be shocked. Connect the shell of the electrical appliance whose shell can conduct electricity to the ground wire. In the case of electric leakage, the current will directly flow into the earth through the ground wire without passing through the body, thereby avoiding electric shock accidents.




In fact, it’s hard to say the specific situation of the zero line and the live line is charged, but from experience, one is that the neutral line is charged due to the bias. This situation is inevitable in the power grid, and the voltage of the neutral line will not be too high, as long as it is not biased. Too outrageous does not affect normal use.




There is also a problem that the neutral wire is broken. Take our ordinary building example, one is that the neutral wire of the home is broken. In this case, the electrical appliances will not work but will not cause damage to the electrical appliances, as long as the user does not privately Disassembly and investigation will generally not cause electric shock injury.




The other is that the neutral wire in the unit circuit is broken, which is rare, but it is very harmful.




Second, the cause of the three-phase neutral line being charged


(1). The neutral line is charged with a lack of good grounding. If it is well grounded, the current will flow into the ground and the meter will not be able to detect it. In short, as the two upstairs said, either the zero line is broken or the contact is not good. However, this is actually the result; not the cause of the neutral line being charged.




 (2) Under normal circumstances, there should be no electricity on the zero line. Therefore, once there is electricity, it must be a fault; the simplest is electromagnetic induction, and the neutral line is not well grounded at this time, and no loop is formed; secondly, the electrical equipment leaks or the phase line touches the shell, but the current is not too large. , So there is no trip.




 (3) The electrical equipment is leaking or the phase line is touching the shell, but the current is not large, so there is no tripping. In a three-phase four-wire power supply system, if the neutral wire is not well grounded or the ground terminal is broken, the consequence is that the potential of the neutral wire is not equal to 0 when the three-phase load is unbalanced, that is to say, the neutral point is biased. shift.




The specific zero line potential is related to the degree of unbalance of the three-phase load. The more unbalanced, the greater the offset of the neutral point and the higher the potential of the zero line. After the zero line potential shifts, the phase voltage of the three phases is generally not 220V. Some phases may exceed 220V, and some phases may be lower than 220V.




If the offset of the neutral point is too large, the phase with the increased phase voltage of the three-phase may cause the electrical appliances to burn out, and the phase with the reduced phase voltage of the three-phase may cause the electrical appliances to fail to work. After the potential of the neutral line rises, when it reaches a certain value, it will cause an electric shock accident if it touches the ground line.




(4) The neutral wire is broken, making the neutral wire live


(5) In the connection to the power grid, some individuals use grounding for the protection of electrical appliances, so that the neutral line is charged.


(6) When a long cable is used for power supply, the induction charging when the electric equipment is not in use, when the equipment is used, this phenomenon will automatically disappear


(7) The neutral line is directly grounded, and the system neutral line is not connected


(8) The zero wire and the live wire overlap


(9) When the three-phase power load is unbalanced, zero potential drift will occur and voltage will be generated.




2. General measures for neutral line electrification


(1) Focus on checking the connection mode and connection effect of each connection of the neutral line.


(2) The neutral line must pass all phase currents. Generally, the area of the neutral line must be large enough, or multiple neutral lines need to be arranged from the main switch box.


(3) Investigate wire breakage caused by various reasons, such as accidental injury caused by external forces such as wall drilling.


(4) If the zero line flickers caused by turning on the light, please check whether the lamp cap has a short circuit and the quality of the light switch. If the zero line of all parts is dotted, please check the zero row of the main switch box; If the zero row is charged, the problem lies in the zero line before the zero row.




3. Specific analysis of specific issues


(1) There is electrical equipment leakage on the line, but the protection device does not operate, making the neutral line live.


Solution: Perform maintenance after power failure, find out the leaking equipment for repair, and find out the cause of the failure of the protection device.


(2) There is a phase grounding on the line, and the main protection device in the power grid is not protected to make the neutral line live.


Solution: After a power failure, first use a shaker to measure the line to see if the line has poor insulation. When measuring, pay attention to disconnect the meter in the line.


(3) The neutral line is broken, and there is electric leakage in the electrical equipment behind the break or there is a large single-phase load operation, which makes the neutral line live.


Solution: After power failure, test whether the zero line is broken, find and repair the broken.


(4) In the zero-connected power grid, some electrical equipment adopts protective grounding and leakage, which makes the neutral line live.


Solution: Distinguish whether the system is connected to the zero system or the grounding system, or repeated grounding in the zero connection system. Then install the ground wire correctly.


(5) In the zero-connected power grid, there are single-phase electrical equipment using "one fire, one ground", that is, no working zero line, so that the zero line is charged.


Solution: Install the N wire, and the PE wire cannot be used as the N wire.




(6) The insulation resistance of some electrical equipment in the power grid has been damaged and leaked, making the neutral line live.


Solution: Check the equipment whose insulation resistance does not meet the specified requirements and repair it.


(7) The working ground connection at the low-voltage side of the transformer has poor contact and large resistance. When the unbalanced current of the three-phase load exceeds the allowable range, the neutral line is charged.


Solution: poor contact is difficult to find, and maintenance should be carried out every year or according to the specified time. Don't be lazy, and carry out maintenance according to the regulations.


(8) High voltage flees into low voltage to make the neutral line live.


Solution: It is difficult to find, and sometimes there will be big problems. The most difficult one to deal with is dangerous to people. Be sure to follow the operating procedures.


(9) The high voltage adopts two-wire one-ground operation mode. When the grounding body is too close to the low-voltage working ground or repeated grounding body, the voltage drop on the high-voltage working ground will affect the low-voltage side working ground and make the neutral line live.


Solution: Find out the reason and lay it according to the corresponding regulations.


(10) The magnetic field induces the neutral line to be charged.


 Solution: Prevent magnetic field induction.


蜜桃av中文字幕在线| 浪潮AV激情高潮国产蜜臀| 极品国产主播粉嫩在线| 久久96国产精品久久| 蜜桃视频一区二区三区| 人妻丰满熟妇aⅴ无码HD| 肉欲麻豆天美传媒| 小雪的L3又嫩又紧又多水图| 亚洲熟妇无码一区二区三区导航| 中文字幕久久熟女蜜桃| А√天堂资源官网在线资源| 国产办公室沙发系列高清| 狠狠色合综情丁香五月| 两个黑人大战嫩白金发美女| 人妻丝袜另类欧美偷拍视频| 我调教同学的放荡麻麻| 亚洲欧洲无码一区二区三区| 97精品人妻一区二区三区香蕉| 刺激的乱亲小说43部分阅读| 国产三级在线观看播放| 乱人伦中文字幕在线视频| 日本肉体裸交XXXXBBBB| 亚洲AV无码乱码在线观看裸奔 | 国产精品久久福利新婚之夜| 精品无码中文字幕不卡| 欧美性爱视频一二三区| 午夜成人爽爽爽视频在线观看| 一本大道东京热无码AⅤ| 被部长灌醉后强行侵犯| 国产真实乱对白精彩久久| 男女啪啪免费观看网站| 偷欢人妻激情系列| 幼儿HIPHOP仙踪林的| 丰满老师引诱我进她身体| 精品人妻AV区波多野结衣| 强开小娟嫩苞又嫩又紧| 午夜理论片免费播放| 中国少妇的BBWWBBWW| 国产成人综合日韩精品无码| 久久水蜜桃亚洲AV无码精品 | Z〇Z〇ZO女人另类Z〇Z○| 国产小受呻吟GV视频在线观看| 免费无码AV污污污在线观看| 无码超级大爆乳在线播放| 中文天堂资源在线WWW| 国产精品18久久久久久不卡| 免费A级毛片无码樱桃视频 | 人妻体体内射精一区二区| 亚洲国产成人无码精品| 超碰成人人人做人人爽| 久久精品人妻一区二区三区一 | 男女车车的车车网站W98免费| 无码精品一区二区三区在线| 91久久精品www人人做人人爽| 国产无人区码SUV| 欧美亚洲国产精品久久高清| 亚洲成A人片在线观看无码下载| 被三个男人绑着躁我好爽| 精品人妻一区二区三区蜜桃| 色综合天天无码网站| 樱桃CHERRY官网| 国产精品综合一区二区三区| 欧美在线视频一区二区三区| 亚洲另类无码专区丝袜| 国产V亚洲V天堂A无码| 女人夜夜春高潮爽A∨片| 亚洲国产美女精品久久久久∴ | 99久久免费国产精品四虎99久久精品免费看国产一区二区 | 夫妇交换聚会群4P疯狂大战| 免费网站看V片在线18禁| 亚洲AV无码片VR一区二区三区| 成人片黄网站色大片免费| 榴莲草莓视频黄丝瓜芭乐秋葵| 亚洲AV无码一区二区高潮| 成在线人AV免费无码高潮喷水| 麻麻让我挺进她的黑森林| 亚洲AV永久精品无码| 国产999精品久久久久久| 欧美性猛交XXXXX按摩欧美| 亚洲中文字幕A∨| 国产熟女真实乱精品视频| 日日狠狠久久偷偷色综合96| 中文字幕四区五区六区蜜桃 | 高潮颤抖大叫正在线播放| 欧美黑人粗暴多交高潮水最多| 亚洲熟妇色XXXXX亚洲| 国产午夜理论片不卡在线观看| 日韩欧美成人免费观看| AV无码不卡一区二区三区| 久久夜色精品国产噜噜麻豆| 亚洲AV综合色区无码二区爱AV| 国产成人亚洲影院在线播放| 人妻少妇精品无码系列| 42岁女子20天断崖式衰老| 久久久久亚洲AV成人网人人网站| 亚洲AV高清在线观看一区二区三| 丰满熟妇大肉唇张开| 日本WWW一道久久久免费榴莲| 7777788888管家婆中特| 狼人在线二线三线区别大吗| 亚洲人成影院在线无码按摩店| 国产日产欧产美韩系列| 玩稚嫩的小屁股眼AV | 色欧美与xxxxx| 草莓影视在线观看视频| 人妻精品丝袜一区二区无码AV| 92国产精品午夜福利| 美日韩一区二区三区| 在线天堂资源WWW在线中文| 久久久久久A亚洲欧洲AV| 亚洲精品永久在线观看| 精品国产乱码久久久久久小说| 亚洲AV无码一期二期三期少妇| 国产精品无码专区| 无码专区国产精品第一页| 国产精品亚洲A∨天堂| 无码少妇一区二区三区浪潮av | 四虎在线观看视频9E9| 成在人线AV无码免费看网站直播| 日本大胆欧美人术艺术| 成av人片一区二区三区久久| 日本高清视频色WWWWWW色| 成人AV无码乱码在线观看无码| 日本毛多水多做受视频| 成人无码H动漫在线网站樱花| 日产无人区二线三线乱码 | 日韩精品无码一区二区三区视频| 边摸边脱吃奶边高潮视频免费| 人体色窝窝7777777| 成在人线AV无码免费| 特级欧美AAAAAAA免费观看| 国产白嫩漂亮美女在线观看| 无码8090精品久久一区| 国产真实乱XXXⅩ| 亚洲欧美成人在线观看| 久久久水蜜桃国产成人网站| 中文字幕一区二区人妻| 欧美日韩一区精品视频一区二区| 把腿张开老子cao烂你动态图| 日韩欧美一区二区三区免费观看 | 精品亚洲成A人无码成A在线观看| 亚洲午夜无码久久久久| 裸体美女洗澡啪啪裸J网站| 99精品国产一区二区电影| 日本爆乳丰满熟妇XXXX| 国产产无码乱码精品久久鸭| 亚洲AⅤ天堂AV天堂无码APP| 精人妻无码一区二区三区蜜桃| 一区二区伊人久久大杳蕉| 免费播看高清大片免播放器一| H罩杯大胸爆乳交在线观看| 日日噜噜夜夜狠狠久久无码区| 国产精品污WWW一区二区三区| 亚洲AV永久天码精品天堂DL| 久久人人97超碰CAOPORE| 91人妻人人澡人爽人精品 | 毛葺葺老太做受视频| YIN荡到骨子里的SAO货| 天堂…在线最新版在线| 黑人巨大BBWBBW| 中文精品久久久久鬼色| 人妻无码不卡中文字幕在线视频| 寡妇两腿间黑黑的毛毛是什么| 亚洲A∨无码男人的天堂 | 野花高清完整版免费观看视频大全| 母亲とが话していま在线观看| 波多野结衣迅雷下载| 无码中文字幕在线播放2| 久久精品亚洲精品国产色婷| DIPTYQUE含羞草香薰| 天天想你在线视频免费观看高清版| 精产国品一二三产区区别在哪儿呢| 在线 亚洲 国产 欧美| 日韩精品无码一本二本三本色| 国产无遮挡无码视频在线观看不卡 | 日产乱码一二三区别免费演员表| 国产午夜激无码AV毛片| 再深点灬舒服灬太大了少妇| 日本少妇XXⅩ熟睡侵犯| 国内AI明星造梦鞠婧祎MV| 最新国产成人无码久久| 首页 动漫 亚洲 欧美 日韩| 久久ER99热精品一区二区| ZOOM与人性ZOOM2区别| 羞羞午夜爽爽爽爱爱爱爱人人人| 久久亚洲日韩AV一区二区三区| 成年午夜免费AⅤ在线观看| 亚洲AV无码久久久久久精品同性| 免费网站看V片在线18禁无码| 国产成人久久精品| 伊人久久精品无码麻豆一区| 色哟哟最新在线观看入口| 精品无人区无码乱码大片国产| WWW一区二区WWW免费| 亚洲 A V无 码免 费 成| 欧美VA国人精品VA| 国产一区二区H无遮挡| A在线视频播放观看免费观看 | 国产美女丝袜高潮白浆| 99久久国产露脸国语对白|